Calibration of the electrochemical methods for the corrosion rate measurement of steel in concrete : NORDTEST project no. 1531-01 / Tang Luping.
In this study, steel bars were embedded in concrete slabs with different chloride introductions (0%, 1.5%, 3% and 6 % by mass of cement) in order to induce corrosion at different rates. The slabs were cast in one laboratory and distributed to three different laboratories for monitoring of corrosi...
Saved in:
| Main Author: | |
|---|---|
| Format: | Book |
| Language: | English |
| Published: |
Borås :
Swedish National Testing and Research Institute,
2002
|
| Series: | SP rapport ;
2002:25 |
| Subjects: | |
| Online Access: | I PDF via Nordtest |
| ISBN: | 9178489164 |
| Summary: | In this study, steel bars were embedded in concrete slabs with different chloride introductions (0%, 1.5%, 3% and 6 % by mass of cement) in order to induce corrosion at different rates. The slabs were cast in one laboratory and distributed to three different laboratories for monitoring of corrosion rate over a period of one year. Four instruments representing two types of electrochemical techniques, that is, linear polarisation technique (GECOR instruments) and galvanostatic pulse technique (GalvaPulse and SP’s instrument), were evaluated in the project through the comparative measurements. Finally, the standard gravimetric method ASTM G1 was used for calibration of the results measured by the non-destructive methods based on the electrochemical techniques... |
|---|---|